We're here to help

    Pressure Pan Testing: How Distribution Efficiency is Calculated

    Follow

    On the Distribution screen, there are 2 radio buttons that can be used to calculate Distribution Efficiency, BPI and Duct Testing (Pressure Pan). This article discusses how the Duct Testing (Pressure Pan) determines distribution efficiency:

    Part 1: Calculate the Q50Ext

    Q50Ext is a calculation that relates the duct leakage to the outdoors

    The formula is Q50Ext= (Ai)b * (square root (sum: ppan readings (pa)))

    where

    Ai = Total free area of all supply & return registers in sq in
    B = empirically derived exponent = .668
    Sum: ppan readings = Sum of pressure pan pressures (pa)

    Part 2: Use the Q50Ext value to Calculate the Efficiency

    Efficiency: 1-(Q50Ext/Fan Air Flow)
    Where the Fan airflow comes from a table of Fan Airflow Multipliers:

    Electronic Draft Furnaces =  130 CFM *(System Size, (BTU/Hr)/10,000 BTU)

    Condensing Furnaces  = 150 CFM *(System Size, (BTU/Hr)/10,000 BTU)

    Central Air Conditioners & Heat Pumps =  400 CFM *(System Size, (BTU/Hr)/12,000 BTU)

    Other Draft Furnaces = 100 CFM (System Size, (BTU/Hr)/10,000 BTU)

    (note: When using P-Pan distribution calculations documented above, per DOE advised standards, the lowest efficiency allowed is 58%. If the calculation is lower than 58% we report it as 58%.)

     

    Was this article helpful?
    0 out of 0 found this helpful

    Comments